Fire Control Instruments Recall for Audio Evacuation Units

Audio Evacuation Unit

Date of Recall
2003-10-30

CPSC Release Number
04-507

Manufactured In
United States

Units
276

Manufacturer
Fire Control Instruments, of Westwood, Mass.

Sold By
To FCI distributors nationwide from January 1998 through April 11, 2003 for a list price of $825.

Problem/Hazard
The AEU can enter a "sleep" mode where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

Injuries/Incidents
FCI has received seven reports of AEUs unexpectedly entering a "sleep" mode. No injuries have been reported.

Description
All FCI AEUs (part number 1100-1171) manufactured prior to April 12, 2003. These AEUs are used in FireVac 7200 System Control Units. A label in the left center of the circuit board reads "FCI 7200" and "AEU." All V5 versions below V5.2-008 and V6 versions below V6.0.14 are included in the recall.

Remedy
FCI will provide a new software chip set for each FireVac System at no charge.

Consumer Contact
Distributors who do not receive the new software chip set or who have additional questions should contact their customer service representative at (800) 633-1311 between 8 a.m. and 5 p.m. ET, Monday through Friday.

Recall Comments

No comments have been posted.
Be the first to add a comment!