Schneider Electric Recalls Surgeloc™ Surge Protection Devices Due to Fire Hazard

Surgeloc Surge Protection Devices

Date of Recall
2020-10-28

CPSC Release Number
21-103

Manufactured In
Mexico

Units
About 47,250

Distributor
Schneider Electric Systems USA, Inc., of Foxboro, Mass.

Sold By
Authorized Schneider Electric distributors from January 2013 through August 2020 and included in factory-ordered panelboards for between $400 and $1,200.

Problem/Hazard
The Surgeloc Surge Protection Device can experience an arc event, which can result in a fire hazard.

Injuries/Incidents
The firm has received one report of an arcing incident that caused smoke damage to the wall in a commercial location.  No injuries have been reported.

Description

This recall involves Schneider Electric Surgeloc Surge Protection Devices.  The 3-wire and 4-wire devices are primarily installed in commercial/industrial applications and may include some residential applications.  They are black rectangular-shaped devices with a green plastic rimmed meter and a white label with "Square D by Schneider Electric," with the date code and the catalog number on the front.  The recalled devices were manufactured from January 1, 2013 (date code 13011) through August 24, 2020 (date code 20352).  The date codes are in the YYWWD format (example: 20452 = year 2020, week 45, day 2 Monday; the day is optional).  The date code is located on the front of the device. Catalog numbers included in the recall include the following:  

Voltage

Surge Current Rating

NQ Panelboard Units - 

Surge Cat No.

120/240 V, 1 Phase,

3-wire + ground

80 kA

SSP01BIA08PBQ1

100 kA

SSP01BIA10PBQ1

120 kA

SSP01BIA12PBQ1

160 kA

SSP01BIA16PBQ1

200 kA

SSP01BIA20PBQ1

240kA

SSP01BIA24PBQ1

208Y/120 V, 3-Phase,

4-wire + ground

Wye

80 kA

SSP02BIA08PBQ1

100 kA

SSP02BIA10PBQ1

120 kA

SSP02BIA12PBQ1

160 kA

SSP02BIA16PBQ1

200 kA

SSP03BIA20PBQ1

240kA

SSP03BIA24PBQ1

240Y/120 V, 3-Phase,

4-wire + ground

High-leg Delta

80 kA

SSP03BIA08PBQ1

100 kA

SSP03BIA10PBQ1

120 kA

SSP03BIA12PBQ1

160 kA

SSP03BIA16PBQ1

200 kA

SSP03BIA20PBQ1

240kA

SSP03BIA24PBQ1

 

Remedy
Replace

Consumer Contact
Schneider Electric at 800-577-7353 from 8 a.m. to 5 p.m. ET Monday through Friday or online at www.se.com/us/surgeloc-safetynotice or www.se.com/us/en/, then click on the link "Product Safety Notice: Surgelogic NQ SurgeLoc Surge Protection Device."

Recall Comments

No comments have been posted.