Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)
Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option
Date of Recall
2018-03-19CPSC Release Number
18-731Manufactured In
MexicoUnits
About 530Distributor
Carrier México, S.A. de C.V.Importer
Carrier Corporation, of Jupiter, Fla.Sold By
Carrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.Problem/Hazard
The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.Injuries/Incidents
Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.Description
This recall involves Carrier WeatherExpert 6-23 ton, 48/50 series, light commercial rooftop HVAC units intended for use in commercial and institutional buildings and that have a factory installed dehumidification feature. The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3). Note that dashes should be counted as digits in the model number. The serial numbers are 1214P to 3317P. The model and serial number can be found on the unit rating plate located on the back of the unit.
Remedy
RepairConsumer Contact
Carrier toll-free at 844-864-8748 from 8 a.m. to 5 p.m. ET Monday through Friday, or online at www.carrier.com and click on "Product Safety Recall" to locate a local Carrier dealer for more information.Recall Comments